Technical Specification – 24 Miners
Qty of B24 Tanks | 1 |
---|---|
B24 Outer Size | 2486*746*530mm |
Input Voltage | 3-phase 350-480V 50/60Hz |
Output Voltage | Single-phase 200-277V 50/60Hz |
Cooling Capacity | 120kW@35°C |
Ambient Temp | -25°C ~ 55°C |
Net Weight (Tank) | 172kg |
Coolant Volume | 750L |
Max Inlet/Outlet Temp | 45/65°C |
Max Power Load | 8kW |
Network | 100Mbps Ethernet switch |
Pipe Diameter | DN65 |
Dry Cooler | FHDC120 |
Dry Cooler Specification
Model | FHDC120 |
---|---|
Cooling Capacity | 120kW |
Circulation Medium | Oil |
Input Voltage | 3-phase 350-480V 50/60Hz |
Max Power Load (kW) | 4 |
Max Inlet/Outlet Temp (°C) | 45/60 |
Reference Temperature (°C) | 35 |
Total Air Volume (m³/h) | 38299 |
Dimensions (mm) | 2186*1874*2100 |
Noise Level @25°C, 16m | 65 |
Shipping Weight (kg) | 769 |
Operating Pressure (MPa) | 0.3 |
EC Fans | √ |
Automatic Speed Control | √ |